Leak sensors
Innovative sensors for detecting leaks and water penetration

Leak sensors

Even tiny amounts of water and other liquids can cause major damage. Especially near moisture-sensitive devices and machines, early detection of leaks using leak sensors is crucially important and prevents failures, damage and costly repairs.

Nahaufnahme eines Schlauches

Sensors

Product
Logo Raychem  chemlex
Assembled lengths (-xx)
Applicable for
Max. Ambient temperature
Assembly
Download Technology
TT1000-xx

1m/__3ft-PC
3m/_10ft-PC
5m/_17ft-PC
7,5m/_25ft-PC
15m/_50ft-PC
25m/_82ft-PC
30m/100ft-PC

water

water-glycol blend

75 °C

horizontal surfaces
– ground
– gutter
– tray

with special fixing technology (ZE) also on vertical surfaces
special constructions

TT1100-OHP-xx

1m/__3ft-PC
5m/_17ft-PC
7,5m/_25ft-PC
15m/_50ft-PC
30m/100ft-PC

water

80 °C

direct on the pipe

special constructions

TT1100-OHP-THIN-xx

1m/__3ft-PC
3m/_10ft-PC
7,5m/_25ft-PC
15m/_50ft-PC
30m/100ft-PC

water

80 °C

direct on the pipe

special constructions

TT-MINI-PROBE

horizontal surfaces
– ground
– gutter
– tray

special constructions

TT-FLAT-PROBE

horizontal surfaces
– ground
– gutter
– tray

special constructions

TT3000-xx

0,3m/__1ft-MC
1,5m/__5ft-MC
4,5m/_15ft-MC
7,5m/_25ft-MC
15m/_50ft-MC
30m/100ft-MC

water
acid
alkali

85 °C

horizontal surfaces
– ground
– gutter
– tray

special constructions

TT5000-xx

0,3m/__1ft-MC
1,5m/_5ft-MC
3m/_10ft-MC
4,5m/_15ft-MC
7,5m/_25ft-MC
15m/_50ft-MC
30m/100ft-MC

Hydrocarbons

(does not react to water)

-20 … 60 °C

horizontal surfaces
– ground
– gutter
– tray

special constructions

TT5001-xx

0,3m/__1ft-MC
1,5m/__5ft-MC
3m/_10ft-MC
7,5m/_25ft-MC
15m/_50ft-MC

solvent

(does not react to water)

-20 … 60 °C

horizontal surfaces
– ground
– gutter
– tray

special constructions

TT-FFS

hydrocarbons on water surfaces

-40 … 60 °C

vertical on water surfaces

special constructions

Ein Raum voller Technischen Schaltschränken / Servern
Avoid expensive water damage and repairs

Leak sensors for use in industry, construction engineering and data centres

The leak warning systems sold by ZIEGLER ENGINEERING are sensor lines connected to an evaluation unit. Unlike point sensors, these detect even the smallest leaks with precision down to the metre over the entire length of the sensor line. An alarm is triggered immediately if a leaking liquid is detected. This enables comprehensive monitoring and the immediate initiation of effective countermeasures. All liquids are detected, and early detection prevents damage and the failure of entire production and process lines. By installing a leak detection system, you can therefore help prevent leak damage in industrial environments or data centres. Our range includes high-quality leak sensors and evaluation units for leak monitoring and leak detection for numerous areas of application.

Leak sensors for water, oil and other liquids

Areas of application of the sensors

The range of applications for leak sensors includes all industries and fields in which liquids could leak and damage sensitive technology. Conventional leak sensors pinpoint even tiny amounts of water and can be installed on horizontal surfaces such as floors, gutters or tubs. Special sensors can also detect hydrocarbons or solvents. In addition to the standard sensor lines, products are also available that float on the water surface, particularly to protect the environment, for example when it comes to detecting oil contamination in water. Important areas of application for leak sensors are commercial buildings, production halls and data centres.

Eine Nahaufnahme eines aufgerollten Kabel
Timely action prevents damage

Leak monitoring

If a leak is detected, quick action is required to minimise downtime, damage and costs. Comprehensive monitoring with leak sensor lines and precise leak detection save valuable time. The sensors are generally equipped with an alarm and detection module that is triggered immediately when a leak is detected and simultaneously transmits the location of the leak. This enables specialist staff to take immediate countermeasures.

Would like some product advice?

Get in touch with our team of experts! Everything you get from ZIEGLER ENGINEERING is from a single source – from planning and commissioning through to maintenance of your electrical trace heating.

Leak sensors for reliable leak detection

Comprehensive leak detection with ZIEGLER ENGINEERING

With a comprehensive range of leak sensors, evaluation units and accessories for leak warning and detection systems, ZIEGLER ENGINEERING is the ideal partner when it comes to avoiding leak damage. We deliver custom solutions for your industry and your company: from project planning to installation and commissioning as well as maintenance and monitoring of your leak warning system. Our team of experts would be happy to advise you and find the perfect solution for your area of application.

Further product categories

Nahaufnahme eines Schaltschrankes
Advanced leak evaluation

Evaluation units for leak warning systems

Evaluation units from ZIEGLER ENGINEERING reliably evaluate leaks.

Nahaugnahme von einer aufgerollten Heizleitung

Heating cables

Our versatile range of heating cables ensures the right temperature and reliable frost protection outdoors.

Ein Mann bastelt an einem Rohr/Kabel

Components and accessories

Optimise trace heating performance with end terminations, connectors, and other accessories.

Frequently asked questions about leak warning systems

Leak detection systems are used to monitor any areas in which leaking liquids could cause damage (e.g. electrics). This includes the monitoring of inaccessible areas and false ceilings. They are often used in data centres (server rooms), for example, and reduce damage or operational system failures.

ZIEGLER ENGINEERING leak detection systems consist of a sensor line or, less commonly, a point sensor (depending on the task), an evaluation unit and installation accessories.

Under raised floors (e.g. data centres): installation under the raised floor with retaining clips. For pipelines: installation underneath the pipeline with fastening tape. Depending on the specific purpose, the system is installed outside or inside the insulation of pipelines or in troughs underneath single or multiple pipelines.

ZIEGLER ENGINEERING leak detection systems locate damage points to the metre. These points can be documented with the time and date of the leak. Fault messages for leak and maintenance alarms.

ZIEGLER ENGINEERING offers its customers all services related to planning, documentation, installation, commissioning and maintenance.

Walter Reichert lächelt mit verschränkten Armen in die Kamera
We provide support for your project

Get in touch with our team of experts

ZIEGLER ENGINEERING is your partner when it comes to electrical trace heating. We offer a wide range of products, vast experience and sound expert knowledge.

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.